Spring-loaded safety valve main fault

1. Leakage In the normal working pressure of the device, the valve flap and seat sealing surface occurred more than the allowable degree of leakage. The reasons are: there is dirt between the valve disc and the sealing surface of the valve seat. Use the lift wrench to open the valve a few times and rinse the dirt off; seal surface damage. Should be based on the degree of injury, grinding or turning grinding method to be repaired; stem bending, tilting or lever deflection with the fulcrum, so that the valve core and valve dislocation. Should be reassembled or replaced; spring elasticity is reduced or lost. Should take to replace the spring, re-adjust the opening pressure and other measures. 2. Valve flap or vibration is mainly due to the spring stiffness is too large. Should use the appropriate stiffness of the spring; adjust the adjustment circle inappropriate, so that the back seat pressure is too high. Should adjust the adjustment ring position; exhaust pipe resistance is too large, causing excessive emissions back pressure. Should reduce the discharge pipe resistance. 3. to the specified pressure does not open the cause of this situation is due to constant pressure is not allowed. Should re-adjust the amount of spring compression or hammer position; valve flap and seat stick. The safety valve should be deflated or discharged manually on a regular basis; the lever of the lever safety valve is stuck or the weight is moved. The hammer should be readjusted and the lever should be moved freely. 4. Do not release the valve flap after the discharge This is the main spring bent stem, valve installation location is not correct or be stuck caused. Should be reassembled. 5. Exhaust pressure continues to rise This is mainly due to the selection of the safety valve displacement Xiaoping equipment safety relief should re-select the appropriate safety valve; valve stem neutral or spring rusty, so that the valve should not be open to The height of the valve stem should be reassembled or replace the spring; exhaust pipe cut enough, should be taken to meet the safety of the exhaust area of ​​the exhaust pipe. 6. less than the required pressure to open the main pressure is not allowed to fixed; spring aging elastic decline. Tighten the adjustment screw should be appropriate or replace the spring.